9.4. LEVEL 3 INSTALLATION

9.4.1. GENERAL
The provisions described in 9.4.1. to 9.4.4. are supplementary and additional to both Level 1 and Level 2 systems described in Sections 9.2. and 9.3.

9.4.2. LOW LOCATION LIGHTING LINES
The width of the low location lighting lines described in 9.2.2. to 9.2.6. should be increased by no less than 50% and the use of Class I material is recommended. Both sides of internal corridors and along the entire length of the escape path should be marked with low location lighting lines.

9.4.3. ADDITIONAL LOW LOCATION LIGHTING LINES IN CORRIDORS AND ON EMERGENCY STAIRS
A further low location lighting line should be added on at least one wall along internal corridors and down the side of emergency stairs. The line should have a minimum width of 100mm of Class II material arid be installed at waist level, between 800mm and 1.1m from the floor to the bottom of the line. This line should supplement the lines provided for in Section 9.4.2. which is then preferably located at the floor or skirting board level.

9.4.4. ADDITIONAL LOW LOCATION DIRECTIONAL SIGNING
Emergency and directional signing should be incorporated in the wall low location lighting lines. They should be no smaller than 80% of the width of the continuous lines. They should be located to correspond to wall mounted emergency directional signs and in no case should be spaced greater than 5m apart.